Property Address:
316 John Street
Kennesaw, GA 30144
![]() |
| Date: 6/7/2006 | Time: 5:15 PM | Report ID: 0101000 |
| Property: 316 John Street Kennesaw, GA 30144 |
Customer: John Baptist |
Real Estate Professional: Agent Your |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
This report will contain statements that are coded by color:
Black: General information or description of item that may be minor.
Green: Describes the location of a certain item, i.e. Main water shutoff
Blue: Items that may need repair or further evaluation.
Red: Items that are a safety concern and/or hazard.
| Age Of Home: Built in 1996 | Client Is Present: Yes | Weather: Clear |
| Temperature: Over 65 |
| Roof Covering: 3-Tab fiberglass | Viewed roof covering from: Binoculars | Sky Light(s): None |
| Chimney (exterior): Composition board |
| 1.0 | ROOF COVERINGS Comments: Inspected |
| 1.1 | FLASHINGS Comments: Inspected |
| 1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS Comments: Inspected |
| 1.3 | ROOF DRAINAGE SYSTEMS Comments: Inspected |
| Siding Style: Beaded Lap | Siding Material: Composite board | Exterior Entry Doors: Fiberglass Insulated glass |
| Appurtenance: Front stoop with steps- stone Rear deck with steps | Driveway: Concrete |
| 2.0 | WALL CLADDING FLASHING AND TRIM Comments: Inspected, Repair or Replace | |||
Wood
trim show signs of deterioration and wood rot. Recommend repair,
caulking and painting where necessary to prevent water intrusion and
deterioration.
|
| 2.1 | DOORS (Exterior) Comments: Inspected |
| 2.2 | WINDOWS Comments: Inspected |
| 2.3 | DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS Comments: Inspected, Repair or Replace | |
Loose stones at front stoop risers. Possible tripping hazard, recommend setting stones.
|
| 2.4 | VEGETATION, GRADING,
DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With
respect to their effect on the condition of the building) Comments: Inspected |
| 2.5 | EAVES, SOFFITS AND FASCIAS Comments: Inspected, Repair or Replace |
| Recommend caulking and painting of soffits and fascias to prevent water intrusion and deterioration. |
| Garage Door Type: One automatic | Garage Door Material: Fiberglass | Auto-opener Manufacturer: SEARS |
| 3.0 | GARAGE CEILINGS Comments: Inspected |
| 3.1 | GARAGE WALLS (INCLUDING FIREWALL SEPARATION) Comments: Inspected |
| 3.2 | GARAGE FLOOR Comments: Inspected |
| 3.3 | GARAGE DOOR (S) Comments: Inspected |
| 3.4 | OCCUPANT DOOR FROM GARAGE TO INSIDE HOME Comments: Inspected |
| 3.5 | GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance) Comments: Inspected |
| Garage door responds to eye sensor but does not respond/reverse when met with resistance. The garage door, when met with resistance, should automatically reverse to prevent any small children from being trapped and/or killed under the closing garage door. Recommend licensed garage door installer for further evaluation and repair as needed. |
| Ceiling Materials: Sheetrock | Wall Material: Sheetrock | Floor Covering(s): Carpet Hardwood T&G Tile |
| Interior Doors: Hollow core | Window Types: Double-hung | Cabinetry: Wood |
| Countertop: Laminate |
| 4.0 | CEILINGS Comments: Inspected | |
Water stain in dining/kitchen
area. Appears to be an older stain. Homeowner states
plumbing repairs were made to upstairs shower.
|
| 4.1 | WALLS Comments: Inspected |
| 4.2 | FLOORS Comments: Inspected |
| 4.3 | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Inspected |
| 4.4 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS Comments: Inspected |
| 4.5 | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| Bedroom door at end of hall does not close properly. Latch does not line up with latch plate. |
| 4.6 | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
| Foundation: Poured concrete | Method used to observe Crawlspace: No crawlspace | Floor Structure: Wood joists |
| Wall Structure: Wood | Roof-Type: Gable | Method used to observe attic: Walked |
| Attic info: Pull Down stairs |
| 5.0 | FOUNDATIONS, BASEMENTS
AND CRAWLSPACES (Report signs of abnormal or harmful water penetration
into the building or signs of abnormal or harmful condensation on
building components.) Comments: Inspected |
| 5.1 | WALLS (Structural) Comments: Inspected |
| 5.2 | FLOORS (Structural) Comments: Inspected | |
Crack in basement is a
settlement crack. There are no vertical cracks on adjacent
foundation wall, therefore, does not appear to be of any issue.
|
| 5.3 | CEILINGS (structural) Comments: Inspected |
| 5.4 | ROOF STRUCTURE AND ATTIC Comments: Inspected |
| Water Source: Public | Plumbing Water Supply (into home): Copper | Plumbing Water Distribution (inside home): Copper |
| Washer Drain Size: 2" Diameter | Plumbing Waste: PVC | Water Heater Power Source: Gas (quick recovery) |
| Water Heater Capacity: 50 Gallon (2-3 people) | Manufacturer: RHEEM |
| 6.0 | PLUMBING DRAIN, WASTE AND VENT SYSTEMS Comments: Inspected |
| 6.1 | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected |
| 6.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Comments: Inspected |
| 6.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) Comments: Inspected |
| Water shut-off and regulator located in basement, front area of home. |
| 6.4 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) Comments: Inspected |
| 6.5 | MAIN FUEL SHUT OFF (Describe Location) Comments: Inspected |
| Main fuel shut off is located at the right side of the house. |
| Electrical Service Conductors: Below ground | Panel capacity: 150 AMP | Panel Type: Circuit breakers |
| Electric Panel Manufacturer: SQUARE D | Branch wire 15 and 20 AMP: Copper | Wiring Methods: Romex |
| 7.0 | SERVICE ENTRANCE CONDUCTORS Comments: Inspected |
| 7.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Comments: Inspected |
| 7.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE Comments: Inspected |
| 7.3 | CONNECTED DEVICES AND
FIXTURES (Observed from a representative number operation of ceiling
fans, lighting fixtures, switches and receptacles located inside the
house, garage, and on the dwelling's exterior walls) Comments: Inspected, Repair or Replace | ||
Exposed
wiring in attic is hot and must be contained in junction
boxes. Recommend licensed electrician to further evaluate and
repair as needed.
|
| 7.4 | POLARITY AND GROUNDING
OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL
RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE Comments: Inspected |
| 7.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) Comments: Inspected, Repair or Replace |
| GFCI in garage does not work. Recommend replacing GFCI to have ground fault protection. |
| 7.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS Comments: Inspected |
| Main disconnect located at right side of home behind a/c units. The subpanel for the house is located in basement at side of stairs. |
| 7.7 | SMOKE DETECTORS Comments: Inspected |
| Heat Type: Forced Air | Energy Source: Gas | Number of Heat Systems (excluding wood): Two |
| Heat System Brand: LENNOX | Ductwork: Insulated | Filter Type: Disposable |
| Filter Size: 14x20 | Types of Fireplaces: Conventional with gas logs | Operable Fireplaces: One |
| Cooling Equipment Type: Air conditioner unit | Cooling Equipment Energy Source: Electricity | Central Air Manufacturer: LENNOX |
| Number of AC Only Units: Two |
| 8.0 | HEATING EQUIPMENT Comments: Inspected | ||
Rust
located in attic furnace. Caused by condensation dripping from
condensate line. Recommend licensed HVAC technician for further
evaluation and repair.
|
| 8.1 | NORMAL OPERATING CONTROLS Comments: Inspected |
| 8.2 | DISTRIBUTION SYSTEMS
(including fans, pumps, ducts and piping, with supports, insulation,
air filters, registers, radiators, fan coil units and convectors) Comments: Inspected |
| 8.3 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM Comments: Inspected |
| 8.4 | CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) Comments: Inspected |
| 8.5 | GAS/LP FIRELOGS AND FIREPLACES Comments: Inspected |
| 8.6 | COOLING AND AIR HANDLER EQUIPMENT Comments: Inspected |
| 8.7 | NORMAL OPERATING CONTROLS Comments: Inspected |
| 8.8 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM Comments: Inspected |
| Attic Insulation: Blown Fiberglass | Ventilation: Ridge vents Soffit Vents | Exhaust Fans: None |
| Dryer Power Source: 220 Electric | Dryer Vent: Flexible Vinyl |
| 9.0 | INSULATION IN ATTIC Comments: Inspected |
| 9.1 | INSULATION UNDER FLOOR SYSTEM Comments: Not Present |
| 9.2 | VENTILATION OF ATTIC AND FOUNDATION AREAS Comments: Inspected |
| 9.3 | VENTING SYSTEMS (Kitchens, baths and laundry) Comments: Inspected |
| Dishwasher Brand: KENMORE | Disposer Brand: IN SINK ERATOR | Exhaust/Range hood: RE-CIRCULATE |
| Range/Oven: KENMORE | Built in Microwave: KENMORE |
| 10.0 | DISHWASHER Comments: Inspected |
| 10.1 | RANGES/OVENS/COOKTOPS Comments: Inspected |
| 10.2 | RANGE HOOD Comments: Inspected |
| 10.3 | FOOD WASTE DISPOSER Comments: Inspected |
| 10.4 | MICROWAVE COOKING EQUIPMENT Comments: Inspected |
![]() Legacy Home Inspections, LLC
2410 Brookgreen Commons |
Customer |
Property Address |
| 2.0 | WALL CLADDING FLASHING AND TRIM | ||||
| Inspected, Repair or Replace | |||||
|
Wood trim
show signs of deterioration and wood rot. Recommend repair,
caulking and painting where necessary to prevent water intrusion and
deterioration.
|
|||||
| 2.5 | EAVES, SOFFITS AND FASCIAS | ||||
| Inspected, Repair or Replace | |||||
|
Recommend caulking and painting of soffits and fascias to prevent water intrusion and deterioration. |
|||||
| 3.5 | GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance) | |
| Inspected | ||
|
Garage door
responds to eye sensor but does not respond/reverse when met with
resistance. The garage door, when met with resistance, should
automatically reverse to prevent any small children from being trapped
and/or killed under the closing garage door. Recommend licensed
garage door installer for further evaluation and repair as needed. |
||
| 7.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | |||
| Inspected, Repair or Replace | ||||
|
Exposed wiring in
attic is hot and must be contained in junction boxes.
Recommend licensed electrician to further evaluate and repair as needed.
|
||||
| 7.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) | |||
| Inspected, Repair or Replace | ||||
|
GFCI in garage does not work. Recommend replacing GFCI to have ground fault protection. |
||||
Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To Legacy Home Inspections, LLC