Inspection Report

John Baptist

Property Address:
316 John Street
Kennesaw, GA 30144

Legacy Home Inspections, LLC

Randy Stephens
2410 Brookgreen Commons
Kennesaw, GA 30144
770-363-3636



Date: 6/7/2006 Time: 5:15 PM Report ID: 0101000
Property:
316 John Street
Kennesaw, GA 30144
Customer:
John Baptist
Real Estate Professional:
Agent Your

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

This report will contain statements that are coded by color:

Black: General information or description of item that may be minor.

Green:  Describes the location of a certain item, i.e. Main water shutoff

Blue:  Items that may need repair or further evaluation.

Red:  Items that are a safety concern and/or hazard.

Age Of Home:
Built in 1996

Client Is Present:
Yes

Weather:
Clear

Temperature:
Over 65




1. Roofing

The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.

Styles & Materials
Roof Covering:
3-Tab fiberglass
Viewed roof covering from:
Binoculars
Sky Light(s):
None
Chimney (exterior):
Composition board
Inspection Items
1.0 ROOF COVERINGS
Comments: Inspected
1.1 FLASHINGS
Comments: Inspected
1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
Comments: Inspected
1.3 ROOF DRAINAGE SYSTEMS
Comments: Inspected
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



2. Exterior

The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.

Styles & Materials
Siding Style:
Beaded
Lap
Siding Material:
Composite board
Exterior Entry Doors:
Fiberglass
Insulated glass
Appurtenance:
Front stoop with steps- stone
Rear deck with steps
Driveway:
Concrete
Inspection Items
2.0 WALL CLADDING FLASHING AND TRIM
Comments: Inspected, Repair or Replace
  Wood trim show signs of deterioration and wood rot.  Recommend repair, caulking and painting where necessary to prevent water intrusion and deterioration.
2.0 Picture 1
2.0 Picture 2
2.0 Picture 3
2.1 DOORS (Exterior)
Comments: Inspected
2.2 WINDOWS
Comments: Inspected
2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS
Comments: Inspected, Repair or Replace
Loose stones at front stoop risers. Possible tripping hazard, recommend setting stones.
2.3 Picture 1
2.4 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)
Comments: Inspected
2.5 EAVES, SOFFITS AND FASCIAS
Comments: Inspected, Repair or Replace
Recommend caulking and painting of soffits and fascias to prevent water intrusion and deterioration.
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



3. Garage

Styles & Materials
Garage Door Type:
One automatic
Garage Door Material:
Fiberglass
Auto-opener Manufacturer:
SEARS
Inspection Items
3.0 GARAGE CEILINGS
Comments: Inspected
3.1 GARAGE WALLS (INCLUDING FIREWALL SEPARATION)
Comments: Inspected
3.2 GARAGE FLOOR
Comments: Inspected
3.3 GARAGE DOOR (S)
Comments: Inspected
3.4 OCCUPANT DOOR FROM GARAGE TO INSIDE HOME
Comments: Inspected
3.5 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance)
Comments: Inspected
Garage door responds to eye sensor but does not respond/reverse when met with resistance.  The garage door, when met with resistance, should automatically reverse to prevent any small children from being trapped and/or killed under the closing garage door.  Recommend licensed garage door installer for further evaluation and repair as needed.



4. Interiors

The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.

Styles & Materials
Ceiling Materials:
Sheetrock
Wall Material:
Sheetrock
Floor Covering(s):
Carpet
Hardwood T&G
Tile
Interior Doors:
Hollow core
Window Types:
Double-hung
Cabinetry:
Wood
Countertop:
Laminate
Inspection Items
4.0 CEILINGS
Comments: Inspected
Water stain in dining/kitchen area.  Appears to be an older stain.  Homeowner states plumbing repairs were made to upstairs shower.
4.0 Picture 1
4.1 WALLS
Comments: Inspected
4.2 FLOORS
Comments: Inspected
4.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Comments: Inspected
4.4 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS
Comments: Inspected
4.5 DOORS (REPRESENTATIVE NUMBER)
Comments: Inspected
Bedroom door at end of hall does not close properly.  Latch does not line up with latch plate.
4.6 WINDOWS (REPRESENTATIVE NUMBER)
Comments: Inspected
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



5. Structural Components

The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home inspector or other persons.

Styles & Materials
Foundation:
Poured concrete
Method used to observe Crawlspace:
No crawlspace
Floor Structure:
Wood joists
Wall Structure:
Wood
Roof-Type:
Gable
Method used to observe attic:
Walked
Attic info:
Pull Down stairs
Inspection Items
5.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)
Comments: Inspected
5.1 WALLS (Structural)
Comments: Inspected
5.2 FLOORS (Structural)
Comments: Inspected
Crack in basement is a settlement crack.  There are no vertical cracks on adjacent foundation wall, therefore, does not appear to be of any issue.
5.2 Picture 1
5.3 CEILINGS (structural)
Comments: Inspected
5.4 ROOF STRUCTURE AND ATTIC
Comments: Inspected
The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



6. Plumbing System

The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.

Styles & Materials
Water Source:
Public
Plumbing Water Supply (into home):
Copper
Plumbing Water Distribution (inside home):
Copper
Washer Drain Size:
2" Diameter
Plumbing Waste:
PVC
Water Heater Power Source:
Gas (quick recovery)
Water Heater Capacity:
50 Gallon (2-3 people)
Manufacturer:
RHEEM
Inspection Items
6.0 PLUMBING DRAIN, WASTE AND VENT SYSTEMS
Comments: Inspected
6.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Comments: Inspected
6.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS
Comments: Inspected
6.3 MAIN WATER SHUT-OFF DEVICE (Describe location)
Comments: Inspected
Water shut-off and regulator located in basement, front area of home.
6.4 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks)
Comments: Inspected
6.5 MAIN FUEL SHUT OFF (Describe Location)
Comments: Inspected
Main fuel shut off is located at the right side of the house.
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



7. Electrical System

The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.

Styles & Materials
Electrical Service Conductors:
Below ground
Panel capacity:
150 AMP
Panel Type:
Circuit breakers
Electric Panel Manufacturer:
SQUARE D
Branch wire 15 and 20 AMP:
Copper
Wiring Methods:
Romex
Inspection Items
7.0 SERVICE ENTRANCE CONDUCTORS
Comments: Inspected
7.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
Comments: Inspected
7.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
Comments: Inspected
7.3 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
Comments: Inspected, Repair or Replace
Exposed wiring in attic is hot and must be contained in junction boxes.  Recommend licensed electrician to further evaluate and repair as needed.
7.3 Picture 1
7.3 Picture 2
7.4 POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE
Comments: Inspected
7.5 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Comments: Inspected, Repair or Replace
GFCI in garage does not work.  Recommend replacing GFCI to have ground fault protection.
7.6 LOCATION OF MAIN AND DISTRIBUTION PANELS
Comments: Inspected
Main disconnect located at right side of home behind a/c units.  The subpanel for the house is located in basement at side of stairs.
7.7 SMOKE DETECTORS
Comments: Inspected
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



8. Heating / Central Air Conditioning

The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to home; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.

Styles & Materials
Heat Type:
Forced Air
Energy Source:
Gas
Number of Heat Systems (excluding wood):
Two
Heat System Brand:
LENNOX
Ductwork:
Insulated
Filter Type:
Disposable
Filter Size:
14x20
Types of Fireplaces:
Conventional with gas logs
Operable Fireplaces:
One
Cooling Equipment Type:
Air conditioner unit
Cooling Equipment Energy Source:
Electricity
Central Air Manufacturer:
LENNOX
Number of AC Only Units:
Two
Inspection Items
8.0 HEATING EQUIPMENT
Comments: Inspected
Rust located in attic furnace.  Caused by condensation dripping from condensate line.  Recommend licensed HVAC technician for further evaluation and repair.
8.0 Picture 1
8.0 Picture 2
8.1 NORMAL OPERATING CONTROLS
Comments: Inspected
8.2 DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: Inspected
8.3 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM
Comments: Inspected
8.4 CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems)
Comments: Inspected
8.5 GAS/LP FIRELOGS AND FIREPLACES
Comments: Inspected
8.6 COOLING AND AIR HANDLER EQUIPMENT
Comments: Inspected
8.7 NORMAL OPERATING CONTROLS
Comments: Inspected
8.8 PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM
Comments: Inspected
The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



9. Insulation and Ventilation

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.

Styles & Materials
Attic Insulation:
Blown
Fiberglass
Ventilation:
Ridge vents
Soffit Vents
Exhaust Fans:
None
Dryer Power Source:
220 Electric
Dryer Vent:
Flexible Vinyl
Inspection Items
9.0 INSULATION IN ATTIC
Comments: Inspected
9.1 INSULATION UNDER FLOOR SYSTEM
Comments: Not Present
9.2 VENTILATION OF ATTIC AND FOUNDATION AREAS
Comments: Inspected
9.3 VENTING SYSTEMS (Kitchens, baths and laundry)
Comments: Inspected
The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



10. Built-In Kitchen Appliances

The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable.

Styles & Materials
Dishwasher Brand:
KENMORE
Disposer Brand:
IN SINK ERATOR
Exhaust/Range hood:
RE-CIRCULATE
Range/Oven:
KENMORE
Built in Microwave:
KENMORE
Inspection Items
10.0 DISHWASHER
Comments: Inspected
10.1 RANGES/OVENS/COOKTOPS
Comments: Inspected
10.2 RANGE HOOD
Comments: Inspected
10.3 FOOD WASTE DISPOSER
Comments: Inspected
10.4 MICROWAVE COOKING EQUIPMENT
Comments: Inspected
The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To Legacy Home Inspections, LLC



General Summary


Legacy Home Inspections, LLC

2410 Brookgreen Commons
Kennesaw, GA 30144
770-363-3636

Customer
John Baptist

Property Address
316 John Street
Kennesaw, GA 30144

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

2 Exterior
2.0 WALL CLADDING FLASHING AND TRIM
 Inspected, Repair or Replace
  Wood trim show signs of deterioration and wood rot.  Recommend repair, caulking and painting where necessary to prevent water intrusion and deterioration.
2.0 Picture 1
2.0 Picture 2
2.0 Picture 3
2.5 EAVES, SOFFITS AND FASCIAS
 Inspected, Repair or Replace
Recommend caulking and painting of soffits and fascias to prevent water intrusion and deterioration.

3 Garage
3.5 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance)
 Inspected
Garage door responds to eye sensor but does not respond/reverse when met with resistance.  The garage door, when met with resistance, should automatically reverse to prevent any small children from being trapped and/or killed under the closing garage door.  Recommend licensed garage door installer for further evaluation and repair as needed.

7 Electrical System
7.3 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
 Inspected, Repair or Replace
Exposed wiring in attic is hot and must be contained in junction boxes.  Recommend licensed electrician to further evaluate and repair as needed.
7.3 Picture 1
7.3 Picture 2
7.5 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
 Inspected, Repair or Replace
GFCI in garage does not work.  Recommend replacing GFCI to have ground fault protection.


Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To Legacy Home Inspections, LLC